Gas Pressure Proving & Ventilation Interlock – Modern Plant Gas Safety Systems https://www.mpgassafetysystems.ie Modern Plant Gas Safety Systems Mon, 16 Nov 2020 17:14:36 +0000 en-GB hourly 1 https://wordpress.org/?v=5.7.12 https://www.mpgassafetysystems.ie/wp-content/uploads/2020/11/cropped-mpi-32x32.png Gas Pressure Proving & Ventilation Interlock – Modern Plant Gas Safety Systems https://www.mpgassafetysystems.ie 32 32 SafeAir CM (GP) https://www.mpgassafetysystems.ie/product/safeair-cm-gp/ https://www.mpgassafetysystems.ie/product/safeair-cm-gp/#respond Wed, 04 Nov 2020 07:59:31 +0000 http://gas.ogx.ie/?post_type=product&p=3344 The SafeAir CM GP offers a simple single panel package for ventilation interlocking a commercial kitchen to aid sites in meeting BS6173:2009 and IGEM/UP19.

The post SafeAir CM (GP) appeared first on Modern Plant Gas Safety Systems.

]]>
It can also monitor for air quality when fitted with the required detectors with carbon dioxide PPM levels displayed on the LCD.

It features gas pressure proving and built-in two-channel current monitor designed for use within commercial kitchens, set up with a simple button press.

Gas proving must be fitted in any commercial kitchen which has appliances fitted without flame failure devices (FFD’s). Gas proving should be considered for the long term benefit and safety of the site when considering other gas standards and that the majority of leaks identified are before the FFD’s.

The easy to use OLED provides clear messages giving real-time information rather than just LED indications.

Fan load sensitivity range on each fan is 30 milliamps to 20 amps (max).

The post SafeAir CM (GP) appeared first on Modern Plant Gas Safety Systems.

]]>
https://www.mpgassafetysystems.ie/product/safeair-cm-gp/feed/ 0
SafeAir (GP) https://www.mpgassafetysystems.ie/product/safeair-gp/ https://www.mpgassafetysystems.ie/product/safeair-gp/#respond Wed, 04 Nov 2020 07:53:32 +0000 http://gas.ogx.ie/?post_type=product&p=3341 The SafeAir (GP) offers a simple cost-effective panel for ventilation interlocking and gas pressure proving in a commercial kitchen.

It is designed for use within commercial kitchens, to aid sites in meeting BS6173:2009 and IGEM/UP19. It can also monitor for air quality when fitted with the required detectors with carbon dioxide PPM levels displayed on the LCD.

The post SafeAir (GP) appeared first on Modern Plant Gas Safety Systems.

]]>
Gas proving must be fitted in any commercial kitchen which has appliances fitted without flame failure devices (FFD’s). Gas proving should be considered for the long-term benefit and safety of the site when considering other gas standards and that the majority of leaks identified are before the FFD’s.

The easy to use LCD provides clear messages giving real-time information rather than just LED indications.

It is a requirement that any mechanical ventilation within a kitchen environment (both supply and extract) is switched on and running before the use of any gas appliances can take place. With the SafeAir (GP), if the ventilation is not switched on, the LCD display informs the operator that the fans are off.

The post SafeAir (GP) appeared first on Modern Plant Gas Safety Systems.

]]>
https://www.mpgassafetysystems.ie/product/safeair-gp/feed/ 0
VGPS-evo https://www.mpgassafetysystems.ie/product/vgps-evo/ https://www.mpgassafetysystems.ie/product/vgps-evo/#respond Wed, 04 Nov 2020 07:48:24 +0000 http://gas.ogx.ie/?post_type=product&p=3339 The VGPS-evo offers ventilation interlocking, gas pressure proving and environmental monitoring in a single panel for use within commercial kitchens helping them meet the requirements of BS 6173:2009 and IGEM/UP19.

The post VGPS-evo appeared first on Modern Plant Gas Safety Systems.

]]>
Very easy to use, the LCD displays clear messages giving real information rather than just LED indications.

Medem gas detectors can be used to monitor the carbon dioxide level to ensure that HSE set levels are not exceeded.

Engineer functions can be used to aid in the setup of the system –displaying real-time inlet and outlet pressure at the gas valve (mbar) Valve lift button, it’s with functions like these that for example a ‘valve let by indication’ check be performed with ease.

The post VGPS-evo appeared first on Modern Plant Gas Safety Systems.

]]>
https://www.mpgassafetysystems.ie/product/vgps-evo/feed/ 0
SEC-K https://www.mpgassafetysystems.ie/product/sec-k/ https://www.mpgassafetysystems.ie/product/sec-k/#respond Wed, 04 Nov 2020 07:39:01 +0000 http://gas.ogx.ie/?post_type=product&p=3336 The SEC-K is a ventilation interlock and gas proving system for commercial kitchens with multiple in-built features which can be used where and when required to help sites meet BS6173/2009 & IGEM UP19.

The post SEC-K appeared first on Modern Plant Gas Safety Systems.

]]>
The recently updated V4 system can monitor for carbon monoxide (CO) and carbon dioxide (CO2) out-of-hours so even when the panel is switched off an alarm can be raised, or ventilation switched on. This provides additional safety monitoring particularly if solid fuel appliances are installed within the kitchen.

Gas proving must be fitted in any commercial kitchen which has appliances fitted without flame failure devices (FFD’s). Gas proving should be considered for the long-term benefit and safety of the site when considering other gas standards and that the majority of leaks identified are before the FFD’s.

Demand-controlled ventilation fail-safe gas valve and relay checking are just some of the new developments making Medem systems continue to be the most reliable, safest and flexible available today.

The post SEC-K appeared first on Modern Plant Gas Safety Systems.

]]>
https://www.mpgassafetysystems.ie/product/sec-k/feed/ 0
CM2L-K https://www.mpgassafetysystems.ie/product/cm2l-k/ https://www.mpgassafetysystems.ie/product/cm2l-k/#respond Wed, 04 Nov 2020 07:31:29 +0000 http://gas.ogx.ie/?post_type=product&p=3333 The CM2L-K is a two-channel current monitor designed for use with Medem ventilation interlock systems.

The post CM2L-K appeared first on Modern Plant Gas Safety Systems.

]]>
Featuring an OLED display and simple button press learn feature makes the CM2L-K current monitor quick and simple to set-up.

Flexibility

Each CM2L-K can be used to interlock 2 fans, the fans are connected by taking the live feed for each fan through the current monitor (before any speed controllers/inverters).

Fan load sensitivity range on each fan is 30 milliamps to 24 amps (max).

CM2L-K with button learn-function without an LCD is also available.

The post CM2L-K appeared first on Modern Plant Gas Safety Systems.

]]>
https://www.mpgassafetysystems.ie/product/cm2l-k/feed/ 0
CM2M-K https://www.mpgassafetysystems.ie/product/cm2m-k/ https://www.mpgassafetysystems.ie/product/cm2m-k/#respond Tue, 03 Nov 2020 15:44:01 +0000 http://gas.ogx.ie/?post_type=product&p=3330 The CM2M-K is a current monitor designed for use with Medem ventilation interlock systems.

The post CM2M-K appeared first on Modern Plant Gas Safety Systems.

]]>
Flexibility

Each CM2M-K can be used to interlock 2 fans, the fans are connected by taking the live feed for each fan through the current monitor (before any speed controllers/inverters).

Fan load sensitivity range on each fan is 30 milliamps to 24 amps (max).

Features and Details:

There are 3 LED indications:

  • 1x Green, for the 12-volt power to the CM2M-K.
  • 2x Red, one for ‘Fan A’ and another for ‘Fan B’ load detection.

When the fans are switched on and the load is detected (installation instructions) the corresponding side’s NO/NC contact will close and the red LED will light, this will flash for the first 15 minutes after current detection and then become solid. The flashing LED helps us to identify a fan intermittently stalling.

The post CM2M-K appeared first on Modern Plant Gas Safety Systems.

]]>
https://www.mpgassafetysystems.ie/product/cm2m-k/feed/ 0
GPPS-evo https://www.mpgassafetysystems.ie/product/gpps-evo/ https://www.mpgassafetysystems.ie/product/gpps-evo/#respond Thu, 29 Oct 2020 16:09:23 +0000 http://gas.ogx.ie/?post_type=product&p=3312 The GPPS-evo is a laboratory gas pressure proving system with the ability to monitor up to four gas sensors.

The gas pressure proving is by Medem’s patented method of dynamically measuring the pressure differential across the solenoid valve when performing a downstream integrity check. This method stops nuisance tripping of the gas supply. The addition of the LCD makes this system very easy to use providing clear messages giving real information rather than just LED indications.

The post GPPS-evo appeared first on Modern Plant Gas Safety Systems.

]]>
Flexibility

The GPPS-evo is designed to perform a downstream integrity check of pipework and appliances which could be left open to atmosphere, such as a laboratory.

In-line with the updated legislation of BB101 and IGEM/UP11/Edition 3 the system can also monitor the CO2 level when fitted with a Medem detector displaying the PPM.

CO2 is considered a primary indicator of air quality, with the latest legislation setting maximum limits for levels within educational facilities.

Carbon Monoxide, Natural Gas and Oxygen depletion detectors can also be monitored.

An auto-stop timer is incorporated to help prevent unauthorised use of the gas out-of-hours.

There are several ‘engineer functions’ which can be used to aid in the set-up of the system.

The post GPPS-evo appeared first on Modern Plant Gas Safety Systems.

]]>
https://www.mpgassafetysystems.ie/product/gpps-evo/feed/ 0