SEC-K


The SEC-K is a ventilation interlock and gas proving system for commercial kitchens with multiple in-built features which can be used where and when required to help sites meet BS6173/2009 & IGEM UP19.

   

Description

The recently updated V4 system can monitor for carbon monoxide (CO) and carbon dioxide (CO2) out-of-hours so even when the panel is switched off an alarm can be raised, or ventilation switched on. This provides additional safety monitoring particularly if solid fuel appliances are installed within the kitchen.

Gas proving must be fitted in any commercial kitchen which has appliances fitted without flame failure devices (FFD’s). Gas proving should be considered for the long-term benefit and safety of the site when considering other gas standards and that the majority of leaks identified are before the FFD’s.

Demand-controlled ventilation fail-safe gas valve and relay checking are just some of the new developments making Medem systems continue to be the most reliable, safest and flexible available today.

Technical Details

Product Dimensions 212mm x 183mm x 97mm
Gas Detection The panel can monitor up to 6 detectors directly and up to 16 when installed with an AD-PP power pack. The current range is:
Methane/Natural Gas (CH4), Propane (C3H8), Carbon Monoxide (CO) Carbon Dioxide (CO2) and Oxygen (O2) Depletion
Alarm Types Fixed low and high alarm peak levels, high alarm activation will latch and isolate the connected gas valve.
Peak Alarms Methane/Natural Gas (CH4) & Propane (C3H8)
• 5% low alarm
• 10% high alarmCarbon Monoxide (CO)
• 20PPM Low Alarm
• 30PPM High Alarm

Carbon Dioxide (CO2) – Selectable
• 1500PPM
• 2200PPM
• 2800PPM
• 4000PPM
• 5000PPM

Oxygen (O2) Depletion
• 19.5% Pre Alarm
• 18% Full Alarm

Warranty Medem’s industry leading five-year warranty is a demonstration of the company’s confidence in the quality and design of our products.

This applies to the main panel; gas detectors carry a two-year warranty.

Service The panel and sensors must be re-commissioned and tested every 12 months as a minimum but with consideration of every 6 months dependant on gas type and environment.

Downloads


File File size
pdf SEC-K v4.0 Instructions mp 782 KB