AGDS-MC


The AGDS-MC v2 is a multi-channel gas detection system designed for use in boiler houses.

Six Medem detectors can be connected (16 with a power pack) for the detection of natural gas, LPG, or carbon monoxide, carbon dioxide and oxygen depletion.

   

Description

In the event of a high alarm from one of the detectors, the system will isolate a connected control valve. Low alarm indication is also given.

Even with the system switched off It can still be used to monitor for carbon monoxide and carbon dioxide via its 0-10v output and BMS relays. Should there be an issue from a solid fuel appliance it can raise an alarm or switch ventilation on via a relay.

The OLED will display appropriate information about alarm situations and detector status.

There are multiple relays which can be used to control remote indications, connect to a BMS system or activate a fan.

See the AGDS-MCM panel for a ‘non-latching’ version which can be used for the control of ventilation systems i.e. indoor car parks on CO detection.

Technical Details

Product Dimensions 255mm x 180mm x 60mm
Gas Detection The panel can monitor up to 6 detectors directly and up to 16 when installed with an AD-PP power pack. The current range is:
Methane/Natural Gas (CH4), Propane (C3H8), Carbon Monoxide (CO) Carbon Dioxide (CO2) and Oxygen (O2) Depletion
Alarm Types Fixed low and high alarm peak levels, high alarm activation will latch and isolate the connected gas valve.
Peak Alarms Methane/Natural Gas (CH4) & Propane (C3H8)
• 5% low alarm
• 10% high alarmCarbon Monoxide (CO)
• 20PPM Low Alarm
• 30PPM High AlarmCarbon Dioxide (CO2)
• 1500PPM High Alarm
• 2200PPM High Alarm
• 2800PPM High Alarm
• 5000PPM High Alarm

Oxygen (O2) Depletion
• 19.5% Pre Alarm
• 18% Full Alarm

Warranty Medem’s industry leading five-year warranty is a demonstration of the company’s confidence in the quality and design of our products.

This applies to the main panel; gas detectors carry a two-year warranty.

Service The panel and sensors must be re-commissioned and tested every 12 months as a minimum but with consideration of every 6 months dependant on gas type and environment.

Downloads


File File size
pdf AGDS-MC v2 Instructions mp 638 KB