Description
Remote emergency stop buttons can be fitted and a fire alarm connected to close the gas valve when activated.
Two change over relays for remote indications or connection to a BMS system.
The AGDS-4 is a four-channel gas detection system designed for use in boiler houses and plant rooms. Up to 4 low voltage sensors for the detection of natural gas, LPG or carbon monoxide can be connected to the panel.
In the event of a high alarm from one of the sensors, the system will isolate/close any connected valve. A low alarm indication is also given.
Remote emergency stop buttons can be fitted and a fire alarm connected to close the gas valve when activated.
Two change over relays for remote indications or connection to a BMS system.
Product Dimensions | 180mm x 130mm x 70mm |
---|---|
Gas Detection | The panel can except a maximum of four detectors. The current range is: Methane/Natural Gas (CH4), Propane (C3H8), Carbon Monoxide (CO) |
Alarm Types | Fixed low and high alarm peak levels, high alarm activation will latch and isolate the connected gas valve. |
Peak Alarms | Methane/Natural Gas (CH4) & Propane (C3H8) • 5% low alarm • 10% high alarmCarbon Monoxide (CO) • 80PPM Low Alarm • 100PPM High Alarm |
Warranty | Medem’s industry leading five-year warranty is a demonstration of the company’s confidence in the quality and design of our products.
This applies to the main panel; gas detectors carry a two-year warranty. |
Service | The panel and sensors must be re-commissioned and tested every 12 months as a minimum but with consideration of every 6 months dependant on gas type and environment. |